The MTL4675 converts a low-level dc signal from a temperature sensor mounted into a 4/20mA current for driving a load. Software selectable features include linearisation, ranging, monitoring, testing and tagging for all thermocouple types and 2-, 3- or 4-wire RTDs. (For thermocouple applications the SAF-CJC plug on terminals 1–3 includes an integral CJC sensor). Configuration is carried out using a personal computer. A single alarm output is provided and may be configured for high or low process alarm or to provide notice of early thermocouple failure.
RTD excitation current:200µA nominal
Cold junction compensation:Automatic or selectable
Cold junction compensation error:≤ 1.0°C
Common mode rejection:120dB for 240V at 50Hz or 60Hz (500ms response)
Series mode rejection:40dB for 50Hz or 60Hz
Output range:4 to 20mA nominal into 600Ω max. (direct or reverse)
Alarm output (configurable):Relay ON in alarm, 250mA @ 35V max
Maximum lead resistance (THC):600Ω
Response time:Configurable - 500 ms default
(Accuracy at 100/200ms - contact MTL):LED indicator
Green: power and status indication:Yellow: alarm indication, on when contacts are closed
Maximum current consumption (with 20mA signal):50mA at 24V
Power dissipation within unit (with 20mA signal):1.2W at 24V