1 channel for PT100 type RTD sensors, 2 alarm outputs The MTL1372 is a single channel signal converter which can accept PT100 RTD inputs and converts the signal to 4-20mA. Ranges are selected by the user using switches on the module. 2 trip amplifiers are also provided with level settings. The module may be powered directly or via the PBUS17.5 power feed in the DIN rail.
1 Input
2 Input -
3 3 wire -
4 wire - 4 4 wire +
9 Trip 1 contact (NO)
10 Trip 1 contact
11 Trip 2 contact (NO)
12 Trip 2 contact
13 Output +
14 Output -
15, E Power supply +ve
16, D Power supply -ve
SPECIFICATION see also common specification
Number of channels One with fully floating input and output
Location of equipment Safe area
Input signal PT100 RTD sensors, 3 or 4 wire connection
Range selection Via switches, refer to instructions
Output signal 4-20mA, current source or current sink
Over-range ;22mA
Response time 500mS
Transfer accuracy at 20 °C 0.2%
Temperature drift 0.01% /°C
Relay characteristics Contact rating: 250V ac, 2A cosØ 0.7, 340V dc, 2A resistive load
Current consumption 80mA max, 55mA typical @24V
Power dissipation 0.6W
Isolation 250V ac or dc between power, field and system circuits.
(tested to 1100Vac)
More MTL 1372 RTD device
MTL1141;MTL1142;MTL1143
MTL1144;MTL1145;MTL1171
MTL1172;MTL1173 ;MTL1211
MTL1249 ;MTL1271;MTL1272
MTL1321;MTL1341;MTL1371
MTL1372;MTL1373;MTL1991