The MTL4676-RTD converts low–level dc signals from temperature sensors mounted in a hazardous–area into 4/20mA currents. Software selectable features include linearisation for standard thermocouple types, ranging, monitoring, testing and tagging. Configuration is carried out using a personal computer. The field connections include cold–junction compensation and do not need to be ordered separately.
Input signal range:–75 to +75mV
Input signal span:3 to 150mV
Cold junction compensation:Automatic or selectable
Cold junction compensation error:≤ 1.0°C
Common mode rejection:120dB for 240V at 50Hz or 60Hz
Series mode rejection:40dB for 50Hz or 60Hz
Safety drive on sensor burnout:Upscale, downscale, or off
Output range:4 to 20mA nominal into 300Ω max. (direct or reverse)
Maximum lead resistance:300Ω
Power requirement, Vs with 20mA signal:60mA at 24V
Power dissipation within unit with 20mA signal:1.4W at 24V