ABB AX460 and AX466 Single and Dual Input pH/Redox (ORP) Analyzers
The AX400 Series pH/Redox (ORP) analyzers and associated electrode systems have been designed for continuous monitoring and control of pH and Redox (ORP). The electrode system can be standardized to the analyzer using the built-in calibration facility and a single point buffering facility provides easy re-calibration after initial standardization.
The analyzer is available in wall-/pipe-mount or panel-mount versions with either one or two programmable, pH or Redox (ORP) input channels, each with its own associated temperature input channel. When making temperature compensated measurements, the sample temperature is sensed by a resistance thermometer (Pt100, Pt1000 or Balco 3K) mounted in the electrode system.
Specification of ABB AX460 and AX466 Single and Dual Input pH/Redox (ORP) Analyzers
pH/Redox (ORP)
Inputs
1 or 2* pH or mV inputs (*AX466 only) and solution earth
1 or 2* temperature sensors (*AX466 only)
Permits connection to glass or enamel pH and reference
sensors and Redox (ORP) sensors
Input resistance
Glass >1 x 1013Ω
Reference 1 x 1013Ω
Range –2 to 16pH or –1200 to +1200mV
Minimum span
Any 2pH span or 100mV
Resolution 0.01pH
Accuracy 0.01pH
Temperature compensation modes
Automatic or manual Nernstian compensation
Range –10 to 150°C (14 to 302°F)
Process solution compensation with configurable coefficient
Range 0 to 100°C (32 to 212°F)
Temperature sensor
Programmable Pt100, Pt1000 & Balco 3KΩ
Control Function – AX460 Only
Controller Type P, PI, PID (Configurable)
Control Outputs Analog
Current output control (0 to 100%)
Time proportioning cycle time
5 to 60s, programmable in 1s steps displayed with doP or roP
Pulse frequency 1 to 120 pulses per minute
Controller action Reverse, direct or bi-directional (programmable)
Proportional band 0.1 to 1000%, programmable in 0.1% increments
Integral action time (Reset) 1 to 7200s in 1s steps, 0 = Off
Derivative 0.1 to 1000s in 0.1s increments
Auto/Manual User-programmable
Analyzer Model Number Description of Analyze Sensor;
AX410 Single Input Conductivity (0 to 10,00 µS y /cm) C e onductivit Not Applicable;
AX411 Dual Input Conductivity (0 to 10,00 µS y /cm) C y onductivit Conductivit
AX416 Dual Input Conductivity and pH/Redox(ORP C ) onductivit pH/Redox(ORP
AX450 Single Input Conductivity (USP C e onductivit Not Applicabl
AX455 Dual Input Conductivity (USP C y onductivit Conductivit
AX460 Single Input pH/Redox(ORP p e H/Redox(ORP Not Applicabl
A X466 Dual Input pH/Redox(ORP p )