WAGO 750-530 8-channel Digital Output 750-530 WAGO I/O System PLC Modules
Number of digital outputs 8
Number of Channels 8
Signal type Digital
Signal type (voltage) 24 VDC
Actuator connection 8 x (1-wire)
Output characteristic high-side switching
Output current per channel 0.5A
Output current short-circuit-protected
Switching frequency (max.) 2 kHz
Load type Resistive, inductive, lamp load
Inductive load switch-off energy dissipation (max.) 0.9J
Output data width (internal) max. 8bits
Supply voltage (system) 5 VDC; via data contacts
Current consumption (5 V system supply) 25mA
Supply voltage (field) 24 VDC (-25 … +30 %); via power jumper contacts (power supply via blade contact; transmission via spring contact)
Current consumption, field supply (module with no external load) 15mA
Isolation 500 V system/field
Indicators LED (A-H) green: Status DO 1 … DO 8
Number of incoming power jumper contacts 2
Number of outgoing power jumper contacts 2
Current carrying capacity (power jumper contacts) 10A
Connection technology: inputs / outputs 8 x CAGE CLAMP®
Connection type 1 Inputs/Outputs
Solid conductor 0.08 … 2.5 mm² / 28 … 14 AWG
Fine-stranded conductor 0.08 … 2.5 mm² / 28 … 14 AWG
Strip length 8 … 9 mm / 0.31 … 0.35 inches
Physical data
Width 12 mm / 0.472 inches
Height 100 mm / 3.937 inches
Depth 67.8 mm / 2.669 inches
Depth from upper-edge of DIN-rail 60.6 mm / 2.386 inches
Mechanical Data
Mounting type DIN-35 rail
Pluggable connector Fixed
Color light gray
Housing material Polycarbonate; polyamide 6.6
Fire load 1.132MJ
Weight 49g
Conformity marking CE
Environmental requirements
Ambient temperature (operation) 0 … +55 °C
Ambient temperature (storage) -25 … +85 °C
Protection type IP20
Pollution degree 2 per IEC 61131-2
Operating altitude 0 … 2000 m / 0 … 6562 ft
Mounting position horizontal (standing/lying); vertical
Relative humidity (without condensation) 95%
Vibration resistance 4g per IEC 60068-2-6
Shock resistance 15g per IEC 60068-2-27
EMC immunity to interference per EN 61000-6-2, marine applications
EMC emission of interference per EN 61000-6-4, marine applications
Exposure to pollutants Per IEC 60068-2-42 and IEC 60068-2-43
Permissible pollutant concentration H2S at a relative humidity < 75% 10ppm
Permissible pollutant concentration SO 2 at a relative humidity < 75% 25ppm
Product Group 15 (I/O System)
eCl@ss 10.0 27-24-26-04
eCl@ss 9.0 27-24-26-04
ETIM 8.0 EC001599
ETIM 7.0 EC001599
PU (SPU) 1 pcs
Packaging type box
Country of origin DE
GTIN 4045454686901
Customs tariff number 8537109170
Environmental Product Compliance
RoHS Compliance Status Compliant,No Exemption