WAGO 750-375 Fieldbus Coupler PROFINET IO 750-375 PLC Modules I/O Systems In Stock
Communication PROFINET IO
Device-specific Supported profiles: PROFIsafe V2, PROFIenergy V1.0; ID code: Vendor ID: 0x011D; Device ID: 0x02EE; Module ID: 0x01000177 (firmware version 01, 02), 0x02000177 (from firmware version 03)
Baud rate 10/100 Mbit/s (10 Mbit/s (ETHERNET protocols), 100 Mbit/s full duplex (PROFINET IO))
Bus segment length (max.) 100 m
Transmission medium Twisted Pair S-UTP; 100 Ω; Cat. 5
Number of modules per node (max.) 250
Number of modules without a bus extension (max.) 64
Input and output process image (fieldbus) max. 512 bytes/512 bytes
Supply voltage (system) 24 VDC (-25 … +30 %); via pluggable connector (CAGE CLAMP® connection)
Current consumption (5 V system supply) 450mA
Total current (system supply) 1,700mA
Supply voltage (field) 24 VDC (-25 … +30 %); via power jumper contacts
Input current (typ.) at nominal load (24 V) 500mA
Power supply efficiency (typ.) at nominal load (24 V) 90%
Isolation 500 V system/field
Number of outgoing power jumper contacts 3
Current carrying capacity (power jumper contacts) 10A
Connection technology: communication/fieldbus PROFINET IO: 2 x RJ-45
Connection technology: field supply 6 x CAGE CLAMP®
Connection technology: system supply 2 x CAGE CLAMP®
Connection technology: device configuration 1 x Male connector; 4-pole
Connection type 1 System/field supply
Solid conductor 0.08 … 2.5 mm² / 28 … 14 AWG
Fine-stranded conductor 0.08 … 2.5 mm² / 28 … 14 AWG
Strip length 8 … 9 mm / 0.31 … 0.35 inches
Physical data
Width 61.5 mm / 2.421 inches
Height 100 mm / 3.937 inches
Depth 71.9 mm / 2.831 inches
Depth from upper-edge of DIN-rail 64.7 mm / 2.547 inches
Mechanical Data
Mounting type DIN-35 rail
Material Data
Color light gray
Housing material Polycarbonate; polyamide 6.6
Fire load 2.809MJ
Weight 151.5g
Conformity marking CE
Environmental requirements
Ambient temperature (operation) 0 … +55 °C
Ambient temperature (storage) -25 … +85 °C
Protection type IP20
Pollution degree 2 per IEC 61131-2
Operating altitude 0 … 2000 m / 0 … 6562 ft
Mounting position horizontal (standing/lying); vertical
Relative humidity (without condensation) 95%
Vibration resistance 4g per IEC 60068-2-6
Shock resistance 15g per IEC 60068-2-27
EMC immunity to interference per EN 61000-6-2, marine applications
EMC emission of interference per EN 61000-6-3, marine applications
Exposure to pollutants Per IEC 60068-2-42 and IEC 60068-2-43
Permissible H2S contaminant concentration at a relative humidity 75 % 10ppm
Permissible SO2 contaminant concentration at a relative humidity 75 % 25ppm
Product Group 15 (I/O System)
eCl@ss 10.0 27-24-26-07
eCl@ss 9.0 27-24-26-07
ETIM 8.0 EC001603
ETIM 7.0 EC001603
PU (SPU) 1 pcs
Packaging type box
Country of origin DE
GTIN 4050821687436
Customs tariff number 85176200000
Environmental Product Compliance
CAS-No. 12060-00-3
1303-86-2
1317-36-8
693-98-1
7439-92-1
79-94-7
REACH Candidate List Substance 2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol
2-methylimidazole
Diboron trioxide
Lead
Lead monoxide
Lead titanium oxide (PbTiO3)
RoHS Compliance Status Compliant,With Exemption
RoHS Exemption 7(a)
7(c)-I
7(c)-II
SCIP notification number (Bulgaria) b6e2dae8-39a6-43b2-9113-59b5f4e59b62
SCIP notification number (Czech Republic) 3f883b10-ebc4-46c8-91b0-b909dbf0bce0