The 1321-RWR100-DP line reactor is designed to serve as a power conditioning device that effectively limits the transmission of extreme over-voltages generated as a by-product of the circuitry of insulated gate bipolar transistors (IGBTs) for Pulse Width Modulation (PWM) in the inverter section of the majority of Variable Frequency Drives (VFDs). These over-voltages, if left unattended, can cause electrical arches in the windings of the motors, known as partial discharges or a corona effect, and these arches can damage insulation and rendering the systems unusable. Another consequence of overvoltages produced in the VFDs is the reflected wave phenomenon, in which as a result of the different impedance levels of the cables and motors, high spikes of energy are reflected to the drive, accelerating the deterioration of the system’s insulation.
BrandAllen-Bradley / Rockwell Automation
Series1321 Power Products
Part Number1321-RWR100-DP
Max. Rated Voltage600V AC, 50/60 Hz frequency
Max. Switching Freq.4 kHz
Temperature Rise115 degrees Celsius
Dielectric Strength4000 Volts rms (5600 volts peak)
Inductance Curve100% at 100% current, 100% at 150% current, 50% at 350% current
Insulation SystemClass H (180 ?°C or better)
ImpregnationHigh bond strength epoxy impregnation, 4000V high dielectric strength
Ambient Temperature45 degrees Celsius
U.L. ListedUL-508 - IP00, IP20, and IP11