Here is a simple English introduction and technical parameters of the Schneider GV2ME21C TeSys GV2 series Motor Circuit Breakers:
The Schneider GV2ME21C is a member of the TeSys GV2 series of motor circuit breakers. It is designed to provide reliable protection for three - phase motors in industrial applications. It can effectively detect and respond to overloads and short - circuits, safeguarding the motor and the entire electrical system. With its user - friendly design, it allows for easy installation and operation, ensuring high - efficiency performance in motor control.
Rated Current: 20A, with a thermal overload protection setting range of 12 - 20A.
Rated Voltage: The rated working voltage\(U_{e}\)is 690V AC, 50/60Hz. The rated insulation voltage\(U_{i}\)is 690V AC, 50/60Hz (conforming to IEC 60947 - 2) and 600V AC, 50/60Hz (conforming to UL 508 and CSA C22.2 No. 14). The rated impulse withstand voltage\(U_{imp}\)is 6 kV according to IEC 947 - 2.
Breaking Capacity:\(I_{cu}\geq100kA\)at 230/240V, 400/415V, 440V, and 500V AC, 50/60Hz;\(I_{cu}=3kA\)at 690V AC, 50/60Hz. The rated operating short - circuit breaking capacity\(I_{cs}\)is 75% at 690V AC, 50/60Hz.
Motor Power: 11kW at 440V, 415V, and 400V AC, 50/60Hz; 4kW at 230V AC, 50/60Hz.
Number of Poles: 3P.
Control Type: Push - button.
Installation Method: Rail installation.
Dimensions: High 107mm, width 44.5mm, depth 78.2mm.
Product Weight: 0.34kg.
Ambient Temperature: -20 - 40°C in the cabinet, -20 - 60°C for the body, and the storage environment temperature is -40 - 80°C.