Welcome to CW Green Tech Limited
[email protected] 86-136 6712 1125
Home      Products Siemens 6DL1131-6BH00-0PH1 SIMATIC ET 200SP HA series
Siemens 6DL1131-6BH00-0PH1 SIMATIC ET 200SP HA series

Siemens 6DL1131-6BH00-0PH1 SIMATIC ET 200SP HA series

  • Product Item : 6DL1131-6BH00-0PH1
  • Product Brand : Siemens
  • INQUIRY

Here are the parameters of 6DL1131-6BH00-0PH1:


  • General Information1:

  • Product Type: SIMATIC ET 200SP HA digital input module, DI 16x24VDC HA.

  • Firmware Version: V1.0, and it can be updated.

  • Terminal Modules: H1, M1, and N0 type terminal blocks are available. The color code of the module - specific color signboard is CC01.

  • Operating Mode1:

  • DI: Yes.

  • Counter: No.

  • Oversampling: No.

  • MSI: No.

  • Redundancy: The redundancy function is available, applicable to M1 - type terminals.

  • Power Supply1:

  • Rated Voltage (DC): 24V.

  • Allowable Voltage Range (DC): 19.2V to 28.8V.

  • Reverse Polarity Protection: Yes.

  • Power Consumption: The rated current consumption is 60mA without sensor power supply, and the maximum current consumption is 120mA without sensor power supply.

  • Sensor Power Supply1:

  • Output Voltage, Min: 18.2V (L + (- 1V)).

  • Short - Circuit Protection: Yes, electronic protection (response threshold 0.7A to 1.3A; up to 2.6A with input - output redundancy).

  • Maximum Output Current per Channel: 0.5A.

  • Maximum Output Current per Module: 2A.

  • Digital Input1:

  • Number of Digital Inputs: 16.

  • Programmable Digital Inputs: Yes.

  • Source / Sink Input: Yes, P - reading.

  • Input Characteristics: It complies with IEC 61131, type 1 and type 3.

  • Pulse Extension: Yes, with lengths of off, 50ms, 100ms, 200ms, 500ms, 1s, 2s.

  • Timestamp: Yes, with a resolution of 10ms and 1ms (accuracy 1ms).

  • Pulse Wave Analysis: Yes, for rising edge, falling edge, and signal edge switching.

  • Input Voltage: The rated value is 24V (DC). For signal "0", it is - 30V to + 5V; for signal "1", it is + 11V to + 30V.

  • Input Current: For signal "1", the typical value is 2.5mA.

  • Input Delay: For standard inputs, it is parameterizable: none / 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20ms.

  • Wire Length: The maximum length of shielded wire is 1000m, and the maximum length of unshielded wire is 600m.

  • Diagnostic Function1:

  • Diagnostic Function: Yes.

  • Alarm: Diagnostic alarm and process alarm are available for each channel.

  • Diagnostic Information: It can be read. Power supply voltage monitoring and sensor power supply monitoring are available. Broken - wire detection is available for each channel, and short - circuit detection is based on M.

  • Diagnostic Display LED: MAINT LED (yellow), power supply voltage monitoring (PWR - LED, green), channel status display (green LED), channel diagnostic LED (red), and module diagnostic LED (green / red).

  • Potential Isolation1:

  • Potential Separation of Channels: There is no potential separation between channels, but there is potential separation between channels and the backplane bus, and no potential separation between channels and the electronic component power supply voltage.

  • Insulation1:

  • Insulation Test: 1500V DC / 1min.

  • Environmental Requirements1:

  • Operating Temperature: - 40 °C to 70 °C for horizontal installation, and - 40 °C to 60 °C for vertical installation.

  • Dimensions and Weight1:

  • Width: 22.5mm.

  • Height: 115mm.

  • Depth: 138mm.

  • Weight: Approximately 135g.