Welcome to CW Green Tech Limited
[email protected] 86-136 6712 1125
Home      Products Siemens 6DL1131-6BL00-0PH1 SIMATIC ET 200SP HA series
Siemens 6DL1131-6BL00-0PH1 SIMATIC ET 200SP HA series

Siemens 6DL1131-6BL00-0PH1 SIMATIC ET 200SP HA series

  • Product Item : 6DL1131-6BL00-0PH1
  • Product Brand : Siemens
  • INQUIRY

6DL1131-6BL00-0PH1

Here is the parameter information of 6DL1131 - 6BL00 - 0PH1:

General Information1

  • Product Type: SIMATIC ET 200SP HA, digital input module, DI 32x24VDC HA.

  • Firmware Version: V1.0, and it can be updated.

  • Compatible Terminal Blocks: H1 and P0 type terminal blocks.

  • Color Code of Nameplate: CC00.

  • I&M Data: Yes, including I&M0 to I&M3.

  • Compatible Software: It can be configured in STEP 7 TIA from version V16, in STEP 7 from version V5.6, in PCS 7 from version V9.0, and in PCS neo from version V3.0. The PROFINET version is GSDML V2.3.

  • Operating Mode1

  • DI: Yes.

  • Counter: No.

  • Oversampling: No.

  • MSI: No.

  • Redundancy Function: No.

  • Power Supply1

  • Rated Voltage (DC) : 24 V.

  • Allowable Range, Lower Limit (DC) : 19.2 V.

  • Allowable Range, Upper Limit (DC) : 28.8 V.

  • Power Consumption : The rated current consumption is 11.5 mA, and the maximum is 15 mA.

  • Sensor Power Supply1

  • Number of Outputs: 32 (when using the terminal block with encoder power supply, type P0).

  • Minimum Output Voltage: 19.2 V.

  • Power Loss1

  • Typical Value: 1.6 W, and the maximum is 2.8 W (when all input points are "1").

  • Address Space1

  • Maximum per Module: 4 byte; + 4 bytes for QI information.

  • Digital Input1

  • Number of Digital Inputs: 32.

  • Programmable Digital Inputs: Yes.

  • Source - type / Sink - type Inputs: Yes, P - reading.

  • Input Characteristics: It complies with IEC 61131, type 1 and type 3.

  • Rated Input Voltage (DC): 24 V. For signal "0", it is - 30 to + 5 V; for signal "1", it is + 11 to + 30 V.

  • Input Current for Signal "1": The typical value is 2.5 mA.

  • Input Delay: When the input voltage is the rated value, for the standard input, it cannot be parameterized. From "0" to "1", the minimum is 3.2 ms and the maximum is 5.3 ms; from "1" to "0", the minimum is 2.9 ms and the maximum is 4.5 ms.

  • Wire Length1

  • Shielded: The maximum is 1000 m.

  • Unshielded: The maximum is 600 m.

  • Sensor Connection1

  • Two - wire Sensors: Yes, and the maximum allowable closed - circuit current is 1.5 mA.

Diagnosis and Monitoring1

  • Diagnostic Function: Yes, and the diagnostic information is readable. It monitors the power supply voltage at the module level. There is no short - circuit protection.

  • Diagnostic Display LEDs: It has a yellow MAINT LED, a green PWR - LED for power supply voltage monitoring, a green LED for channel status display, and a green / red DIAG - LED for module diagnostics.

  • Potential Isolation1

  • Between Channels and Electronic Component Power Supply Voltage: No.

  • Insulation Test1

  • Tested with 1500 V DC/1 min.

  • Operating Environment Temperature1

  • Horizontal Installation: - 40 °C to 70 °C.

  • Vertical Installation: - 40 °C to 60 °C.

  • Dimensions1

  • Width: 22.5 mm.

  • Height: 115 mm.

  • Depth: 138 mm.

  • Weight1