6DL1134-6TH00-0PH1
Here is the parameter information introduction of 6DL1134-6TH00-0PH1:
General Information
Product Type: SIMATIC ET 200SP HA, analog HART input module, AI 16XI 2 - wire HART HA.
Suitable for Terminal Blocks: H1, M1.
Color Code: CC01.
Channel Diagnostics: Available.
Resolution: 16 - bit.
Accuracy: ±0.1%.
Firmware
Version: V1.1.
Updatable: Yes.
Power Supply1
Rated Voltage (DC): 24 V.
Allowable Range (DC): 19.2 V to 28.8 V.
Input Current1
Rated Current: 80 mA (without sensor power supply).
Maximum Current: 90 mA (without sensor power supply).
Sensor Power Supply1
24 V Supply: Yes.
Short - circuit Protection: Yes, electrical type (response threshold 0.7 A to 1.5 A).
Maximum Output Current per Channel: 0.5 A.
Maximum Output Current per Module: 2 A.
Power Loss
Typical Value: 4.5 W (without sensor power supply).
Address Space
Maximum per Module: 34 byte (32 - byte input, 2 - byte for query interface QI information) for non - HART mode.
Maximum per Module with HART: 74 byte (32 - byte input, 2 - byte for QI information, 40 - byte for HART).
Maximum per Module with MultiHART: 41 byte (32 - byte input, 2 - byte for QI information, 6 - byte input for HART and 1 - byte output for MultiHART command).
Analog Inputs
Number of Inputs
Allowed Input Current (Damage Limit): Maximum 30 mA.
Input Ranges: 0 - 20 mA and 4 - 20 mA, both with 16 - bit resolution including sign. The input resistance is 250 Ω for both ranges.
Signal Processing
Measurement Principle: Integrated (Sigma - Delta).
Resolution: Up to 16 - bit including sign. 15 - bit at 0 - 10 mA and 60 Hz rejection frequency.
Parameterizable Integration Time: Yes, for each channel.
Parameterizable Filtering: Yes, selectable for each channel: none, weak, medium, strong.
Linearity Error: ±0.01% related to input range.
Temperature Error: ±0.005% / K related to input range.
Crosstalk between Inputs: Minimum 60 dB.
Repeatability at 25 °C: ±0.05% related to input range.
Basic Error Limit at 25 °C: ±0.1% related to input range for current.
Alarm/Diagnostic/Status Information
Diagnostic Function: Yes.
Diagnostic Alarm: Yes.
Limit Value Alarm: Yes, two upper and two lower limit values respectively.
Power Supply Voltage Monitoring: Yes.
Diagnostic Display LEDs: MAINT LED (yellow), PWR - LED (green for power supply monitoring), channel status display LEDs (green), red LED for channel diagnostics, and DIAG - LED (green / red for module diagnostics).
Potential Isolation
Insulation Test: 1500 V DC / 1 min.
Environmental Conditions1
Operating Temperature: - 40 °C (minimum for both horizontal and vertical installation).
Dimensions
Width: 22.5 mm.
Height: 115 mm.
Depth: 138 mm.
Weight1
Approximately: 148g.
Other Information
Product Lifecycle: PM300: active product.
Country of Origin: Germany.
Compliance with RoHS Directive: Since 23.05.2017.
EAN: 4047622433263.
UPC: 804766483844.