1768-L45S is a Compact GuardLogix series safety processor of Allen-Bradley under Rockwell Automation.
The following are its technical parameters:
Electrical parameters
Voltage type: DC
LED indication input: None
LED indication output: None
Maximum number of 1768 modules: 4
Maximum number of 1768 motion modules: 4
Maximum number of I/O groups: 3
Maximum number of 1769 I/O modules: 30
Power consumption: 9.5W
Slot width: 1.5
Power consumption: 50.4W
1768 current consumption: 5.6A@5V DC
Total current consumption of 1768 and 1769: 7.6A@5V DC
Backplane current consumption: 2.1A@24V DC
Available user memory: 3MB standard, 1MB Safety
Programming language: Standard tasks support all languages, safety tasks support relay ladder diagrams, safety application instructions
Local control protection: No
Fail-safe model: No
Communication media: Fiber optic No, wireless No, copper cable Yes
Communication protocol: RS - 232
Maximum 1768 communication modules: 2
Power supply distance rating: 4 modules
1769 current consumption: 2.0A@5V DC
Power supply: 1768 - PA3, 1768 - PB3
Communication port wiring category: Class 2
Module expansion capacity: two 1768 modules, sixteen 1769 modules
Isolation voltage: 30V (continuous), functional insulation type, tested at 500V AC for 60s, RS - 232 is isolated from the system
Mechanical parameters
DIN rail installation: Supported
Weight: About 0.45kg
With display: No
With PC connection: Yes
Module position: DIN rail or panel installation
Communication port: RS-232, fully isolated, 38.4kbps max
Panel mount screw torque: 1.16N・m (10lb.in), using M4 or #8 screws
Width: 89.6mm
Height: 131.6mm
Depth: 122.1mm
With base plate: No
For front mounting: Yes
Enclosure type rating: No (open frame)
Environmental parameters
Shock (operating): 30g
Ambient air temperature (maximum): 60°C
Operating temperature: 0°C
Storage temperature: -40°C
Vibration: 5g@10 - 500Hz
Relative humidity: 5 - 95%, non-condensing
Emission: CISPR 11 (IEC 61000 - 6 - 4)
Electrical fast transient burst (EFT/B) immunity: ±4kV, 5kHz on communication ports
Electrostatic discharge (ESD) immunity: 6kV contact discharge, 8kV air discharge
Surge transient immunity: on communication ports ±2kV Line-to-Ground (Common Mode)
Conducted RF Immunity: 150kHz - 80MHz, 10V rms, 1kHz sine wave, 80% AM
Radiated RF Immunity: 80 - 2000MHz, 10V/m, 1kHz sine wave, 80% AM; 900MHz, 10V/m, 200Hz, 50% pulse, 100% AM; 1890MHz, 10V/m, 200Hz, 50% pulse, 100% AM; 2000 - 2700MHz, 3V/m, 1kHz sine wave, 80% AM
Approvals
Explosion-proof: None
North American Temperature Code: T4
IEC Temperature Code: T4