This isolator detects loop current and converts it to 4~20mA signals, and also provides transmitters with power. It allows transmission of HART communication signals. The input, output, and power supply are galvanically isolated from each other.
Power supply:18 ~ 60 V DC
Input signal:4 ~ 20mA, HART
Insulation resistance:approx. 50Ω
Available voltage:open-circuit voltage ≤ 26V; voltage: ≥ 22V at 20mA
Output signal:4 ~ 20mA, HART
Load resistance:RL ≤ 550 Ω
Accuracy:0.1%F.S.
Temperature drift:30 ppm/℃
Response time:≤ 2 ms
Power dissipation:1.8 W
Operation temperature:-20 ℃ ~ +60 ℃
Storage temperature:-40 ℃ ~ +80 ℃
Connection method:Screw connection
Dimension:12.8mm (W) × 110mm (H) × 117mm (D)
NPGL-CM111D
NPGL-CMD111D
NPGL-C118D
NPGL-C11
NPGL-C111
NPGL-C1111D
NPGL-C11111D
NPGLB-CM11D
NPGLB-CMD111D
NPGL-C11D
NPGL-C111D