Temperature input isolated barrier, it converts the thermocouple/thermal resistance signals from a hazardous area into 4~20mA signals to a safe area by isolation. It has external cold junction compensation terminals. It needs an independent power supply. The input, output, and power supply are galvanically isolated from each other.
Power supply:20 ~ 30 V DC
Output signal:4 ~ 20 mA
Load resistance:RL ≤ 500 Ω
Compensation accuracy:1°C (Temperature compensation range: -20°C ~ +60°C)
Response time:≤ 500 ms
Power dissipation:≤ 1.1 W
Insulation resistance:≥ 100 MΩ (Input /Output/Power supply)
Operation temperature:-20 ~ +60 ℃
Storage temperature:-40 ~ +80 ℃
Connection method:Screw connection
Dimension:17.8mm (W) × 110mm (H) × 117mm (D)
NPEXA-C01H
NPEXA-K01
NPEXA-C11T1
NPEXA-C011H
NPEXA-C0D11
NPEXA-C11H
NPEXA-C111H
NPEXA-C1D11
NPEXA-C21
NPEXA-C211
NPEXA-C2D11
NPEXA-C11L
NPEXA-C21L
NPEXA-C21T1