The technical parameters of ADV151-P00/B5D10 are as follows:
1. Number of channels: 32 channels
2. Rated input voltage: 24V DC (current sinking/current sourcing)
3. Input on-voltage: 18 to 26.4V DC
4. Input off-voltage: 5.0V DC or lower
5. Input current: 4.1mA±20%/channel at rated input voltage
6. Maximum allowable input voltage: 30.0V DC
7. Withstand voltage between input signal and system: 2kV AC, for 1 minute
8. Withstand voltage between common terminals: 500V AC, for 1 minute, shared by every 16 channels
9. Input response time: 8ms or less for state input; for button input, the minimum on-detection time is 20ms, and the maximum on-off cycle is 25Hz
10. Maximum current consumption: 500mA (5V DC)
11. Weight: Approximately 0.3kg
12. External connection: Double clamp terminal block with surge absorber (model ATB5D-10), special cable (AKB331), Mil connector cable can also be used