FOXBORO is now a brand of French Schneider, which mainly manufactures instruments for industrial control and process automation.
Schneider Electric (French: Schneider Electric) was founded in 1836, is a large energy management company, one of the optimization solutions provider, the main products include circuit breakers, sensors, controllers, etc., for the countries of the energy facilities, industry, data centers and networks, buildings, to provide total solutions. Which in the energy, infrastructure, industrial process control, building automation, data centers and networks and other markets.
FOXBORO main products: FOXBORO sensors, FOXBORO circuit breakers, FOXBORO control valves, FOXBORO actuators, FOXBORO converters, FOXBORO relays, FOXBORO controllers, FOXBORO recorders and indicators, FOXBORO thermocouple bushing, FOXBORO DEWCEL Dew point meters, FOXBORO filter regulators, FOXBORO pneumatic transmitters and more.
Standard Specifications
Automatic Temperature
100 Ω platinumRTD in-1 and -2 (standard) versions and 1000 Ω platinumRTD in-3 and-4(intelligent)
Compensation (ATC)
versions.
Cable Temperature Limit
85C(185F)
Sensor Immersion Depth
76 mm (3 in) minimum.
Process Wetted Parts Materials:
Body
PVDF (polyvinylidene fluoride).
Measuring Electrode
pH
Flat Glass.
ORP
Platinum or gold, as specified.
Reference Electrode
Ceramic Junction.
O-Ring
EPR(Ethylene Propylene Rubber).
Reference Electrode
Ceramic, double junction with KC1, nonflowing, gelled electrolyte (Ag, AgC1halfcell).
Cable
Integral 3 m (10 ft) No.22 AWG with stripped and tinned ends. Intelligent sensors have lugs as standard.
Sensor Mounting
1NPT on both ends with a 1.125-inch wrench flat on body.
Sensor Torque
Maximum torque specification is31 N*m (23 lb*ft).
Measurement Range pH
2 to 12 pH. (Sensor can be used with transmitters and analyzers that are ranged from 0-14 pH)
ORP±2000 mV
Mass 0.35 kg (0.75 lb) including cable.
Electromagnetic
The 871A Sensor, when its cable is connected through rigid metal conduit as recommended to 873PH,
Compatibility (EMC)
873APH, 873DPX (220 Vac, 240 Vac Metal Enclosures only), 875PH, or 870ITPH Analyzers/Transmitters,
complies with the requirements of the European EMC Directive 89/336/EEC.
FOXBORO PH/ORP Sensor 871A Series Introduction
The 871A-1 and -2 (standard) sensors are designed for use with the 873PH and 873DPX analyzers, and can also be used with the 875PH analyzer and 870ITPH transmitter.
The 871A-3 and -4 (Smart) sensors are designed for use with the 875PH Smart Analyzer and 870ITPH Smart Transmitter. They provide the added feature of on-line diagnostics to signal the user in the event of any of several common sensor failures. These sensors can be installed into the process in a variety of ways. They have a 1-inch external NPT connection at both the electrode and cable ends. The sensors can be plugged directly into the production line, or the sensors can be connected to other standard pipe sizes with a variety of accessories. Field installations in weirs, drains, ponds, and tanks are possible by coupling the 1-inch NPT connection at the cable end of the sensor to the desired length of 1-inch pipe and then lowering the assembly into the process to be monitored.
These sensors utilize a sealed electrode design, eliminating concerns about the integrity of the electrode system. When used in conjunction with a smart analyzer or transmitter, the smart sensor design can send a signal to the user informing them of any loss or breach of electrode system integrity. All sensors are factory tested to ensure proper performance when installed.
MODEL CODE
Description
Model
pH and ORP Sensor
871A
Signal Conditioning(a)
Standard Configuration,No Preamplifier
1234
Standard Configuration,Integral Preamplifier
Intelligent Configuration, No Preamplifier
Intelligent Configuration,Integral Preamplifier
Measuring Electrode and Material
pH, Flat Glass
FDE
ORP,Platinum
ORP, Gold
Optional Integral Cable Selection
See Notes (b) and (c)
135
Nonstandard Integral Cable Length to 15 m (50 ft); specify length (d) (c)
Nonstandard Integral Cable Length to 15 m (50 ft), specify length; select with871A-2 Sensor only
Terminated in Connector Plug (e)
Standard 3 m (10 ft) Integral Cable, select with871A-2 Sensor only
-7
Terminated in Connector Plug (f)
Examples: 871A-2F-7;871A-3F-3(40ft required)
FOXBORO 871A-1
FOXBORO 871A-2
FOXBORO 871A-3
FOXBORO 871A-4
FOXBORO 871A-1D-1
FOXBORO 871A-1F-3
FOXBORO 871A-2F-1
FOXBORO 871A-4F-3
FOXBORO 871A-2F-3
FOXBORO 871A-2F-7
foxboro 871a-2d-1