  • Product Item : 1797-PSIE
  • Product Brand : Allen-Bradley
  • INQUIRY

The Allen-Bradley 1797-PSIE is a Power supply module that is part of the 1797 Flex Ex product family. This module features an input voltage range of 85-253 VAC along an input frequency of 47-63 Hz. It has Four (4) output ports with each port delivers an output power rating of 8.5W.


The 1797-PSIE has a flame proof enclosure with increased safety input/output terminations. Wire entry and exit ports of this module is sealed, having an M20 x 1.5 gland that is compatible with 6-12 mm (0.267…0.472 in.) wire diameter for the inputs and M16 x 1.5 gland that is compatible with 4-8 mm (0.157…0.315 in.) wire diameter for the outputs. Each output ports are Intrinsically-safe, galvanically isolated from the source and at the same time independently IS limited.

Technical specifications for 1797-PS1E

ManufacturerRockwell Automation

Thermal Dissipation71.67 BTU/hr

Power Dissipation21 W

Output Power4 x 8.5 W

Current Consumption0.9 A

Input Frequency47…63 Hz

Voltage Range85…253V AC

Input Connectors85…253V AC, Um = 253V AC Terminals 1, 2, 4, 5 (earth symbol)

Part Number/Catalog No.1797-PS1E

Input Power55 W

BrandAllen-Bradley

Product Description:FLEX Ex 85…253V AC In/Quad-Ex DC Out Power

Input power entrance:Increased safety

Output connectors:Terminals 10…17

Input power to output power isolationGalvanic to DIN EN50020

Product TypeFLEX Ex Power Supply

Voltage9.5V

Weight 7.7 kg


The 1797-PSIE comes with a protection factor of IP65. When the power supply outputs have been exposed to non-intrinsically safe signals, the 1797-PSIE, cannot be used in intrinsically safe installations. This module is applicable for installation in Zone 1 where the permissible ambient temperature is f -20…70 °C; Zone 22 that corresponds with the category 3D acc. to directive 94/9 EC and is marked with a type label accordingly. When used with an ambient temperature of 60 Degree Celsius, power supply leads must be designed for service temperature of 80 Degree Celsius.