The Allen-Bradley 1756-OA8E is a ControlLogix discrete output module. This module comes with Eight (8) output channels that delivers a nominal output voltage of 120 VAC with operating range of 74-132 VAC, 47-63 Hz. This module has Two (2) output groups of Four (4) channels each with output current of 2 A @ 60 degrees C (140 degrees F) and output current per group of 2 A @ 60 degrees C (140 degrees F); 4 A @ 30 degrees C (86 degrees F) / 2 A @ 60 degrees C (140 degrees F) with linear derating and output current per module of 8 A @ 30 degrees C (86 degrees F) / 4 A @ 60 degrees C (140 degrees F) with linear derating. The 1756-OA8E has an output delay time of 9.3 ms @ 60 Hz or 11 ms @ 50 Hz for Off to On and On to Off output transitions. This module may be installed to any available slot of the 1756 chassis with a current draw of 200 mA @ 5.1 VDC and 250 mA @ 24 VDC and total backplane power requirement of 7.02 Watts. It has a maximum power dissipation of 5.5 Watts @ degrees C (140 degrees F) and Thermal dissipation of 18.76 BTU/hr. There is no limit to the number of instances of the 1756-OA8E. Instances of this module may be installed to any available slots of the 1756 chassis. It is also provided with individual channel protection as each channel of the module comes with electronic fusing. For connection or signal wires, the 1756-OA8E require use of 1756-TBNH or 1756-TBSH Removable Terminal Block (RTB).

Technical specifications for 1756-OA8E

ManufacturerRockwell Automation

BrandAllen-Bradley

Part Number/Catalog No.1756-OA8E

ManufacturerRockwell Automation

SeriesControlLogix

Part Number/Catalog No.

Module TypeElectronic Fused AC Output Module

1756-OA8ESeries

Outputs8-Point Electronic Fusing

ControlLogixModule Type

Voltage120 Volts AC

Digital AC Sourcing OutputNo. of outputs

Operating Voltage Range74-132 Volts AC

Eight (8) Electronically-fused, output channelsOutput Voltage, nominal

Maximum Output Current Rating-Point2 Amps at 60 degrees Celsius

120 VACOutput Voltage range

Maximum Output Current Rating-Module8 Amps at 30 degrees Celsius and 4 Amps at 60 degrees Celsius

74-132 VAC, 47-63 HzOutput Current per channel, nom.

Power Dissipation (Max)5.5 Watts at 60 degrees Celsius

2 A @ 60 degrees C (140 degrees F)Output Current per group, max.

Backplane Current at 5 Volts200 milliamps

4 A @ 30 degrees C (86 degrees F) linear derating; 2 A @ 60 degrees C (140 degrees F) linear deratingOutput Current per module, max.

Backplane Current at 24 Volts250 milliamps

8 A @ 30 degrees C (86 degrees F) linear derating; 4 A @ 60 degrees C (140 degrees F) linear deratingBackplane Current, 5.1VDC

Removeable Terminal Block(s)1756-TBNH, 1756-TBSH

200 mABackplane Current, 24VDC

Isolation Voltage50 Volts Continuous

250 mAPower Dissipation

EnclosureNone

5.5 W @ 60 degrees C (140 degrees F)Output Signal delay

UPC10612598171399

9.3 ms @ 60 Hz; 11 ms @ 50 HzEnclosure type rating

None (open-style)Removable Terminal Block