The Allen-Bradley 1746-OA8 is an SLC 500 AC output module. This module is part of discrete output modules, used to energize electrical loads that operate at an operating voltage range of 85-264 VCA with frequency of 47-63 Hz. The module’s nominal output voltages are 120VAC and 240VAC and occupies a single slot of the 1746 chassis.
Each channel of the 1746-OA8 delivers a continuous output current of 1.0 A @ 30 °C (86 °F) or 0.50 A @ 60 °C (140 °F) while the maximum continuous output current per module is 8.0 A @ 30 °C (86 °F) and 4.0 A @ 60 °C (140 °F). Additionally, each channel has an ON signal delay of 1 ms for resistive load and maximum OFF delay signal of 11 ms for resistive load as well.
The 1746-OA8 draws backplane current amounting to 185 mA @ 5VDC with ON state output voltage drop of 1.50V @ 1.0 A. The module’s minimum load current is 10 mA with maximum OFF state leakage output current of 2 mA. The module’s maximum surge current per point is 10 A for 25 ms.
ManufacturerRockwell Automation
Module TypeDiscrete AC output module
SeriesSLC 500
Part Number/Catalog No.1746-OA8
BrandAllen-Bradley
No. of groups2
No. of channels per group4
Nom Output Voltage120 / 240 VAC
Output Voltage Range85-264 VAC
Backplane current consumption185 mA
ON Signal delay, max. resistive load1 ms
OFF Signal delay, max. resistive load11 ms
Continuous current per point1.00 A at 30 °C (86 °F); 0.5 A at 60 °C (140 °F)
Continuous current per module8.0 A at 30 °C (86 °F); 4.0 A at 60 °C (140 °F)
On-state voltage drop, max1.5V at 1.0 A
Surge current per point10 A for 25 ms
Voltage Range85-265 Volts AC
Outputs8
Current/Output at 30 Celsius1 amp
Current/Output at 60 Celsius0.5 amp
Backplane Current (5 Volts)185 milliamps
Current/Module (30 Celsius)8 amps
ApplicationsGeneral Purpose
Step Response60 milliseconds in, 2.5 milliseconds out