The KL3172 analog input terminal processes signals in the range of 0 to 2 V. The voltage is digitized to a resolution of 16 bits and is transmitted, electrically isolated, to the higher-level automation device. The input channels of the Bus Terminal have differential inputs and a common, internal ground potential. With the high measurement accuracy of ±0.05% (relative to full scale value), the terminal is optimized for high-precision control processes, such as dosing, filling, or quality assurance. The Bus Terminal has two channels within a housing. LEDs indicate data exchange with the Bus Coupler.
Product information
Number of inputs:2
Power supply:via the K-bus
Signal voltage:0…2 V
Technology:differential input
Internal resistance:> 70 kΩ
Common-mode voltage UCM:max. 10 V
Conversion time:140 ms, configurable
Filter:50 Hz, configurable
Resolution:16 bit
Measurement error/uncertainty:< ±0.05% (relative to full scale value)
Electrical isolation:500 V (K-bus/signal voltage)
Current consumption power contacts:–
Current consumption K-bus:typ. 85 mA
Bit width in the process image:input: 2 x 16 bit data (2 x 8 bit control/status optional)
Special features:increased measuring accuracy
Weight:approx. 70 g
Operating/storage temperature:0…+55°C/-25…+85°C
Relative humidity:95%, no condensation
Vibration/shock resistance:conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission:conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.:IP20/variable
Approvals/markings:CE, UL, ATEX, IECEx
Pluggable wiring:for all KSxxxx Bus Terminals
Design form:compact terminal housing with signal LEDs:terminal housing with pluggable wiring level
Material:polycarbonate
Dimensions (W x H x D):12 mm x 100 mm x 68 mm
Installation:on 35 mm DIN rail, conforming to EN 60715 with lock
Side by side mounting by means of:double slot and key connection
Marking:labeling of the BZxxx series
Wiring:solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver
Beckhoff Bus Terminal 2-channel analog input KL3182
Beckhoff Bus Terminal 2-channel analog input KL3061
Beckhoff Bus Terminal 2-channel analog input KL3062
Beckhoff Bus Terminal 2-channel analog input KL3162
Beckhoff Bus Terminal 2-channel analog input KL3064
Beckhoff Bus Terminal 2-channel analog input KL3468
Beckhoff Bus Terminal 2-channel analog input KL3001
Beckhoff Bus Terminal 2-channel analog input KL3012
Beckhoff Bus Terminal 2-channel analog input KL3112
Beckhoff Bus Terminal 2-channel analog input KL3044
Beckhoff Bus Terminal 2-channel analog input KL3448
Beckhoff Bus Terminal 2-channel analog input KL3041
Beckhoff Bus Terminal 2-channel analog input KL3042
Beckhoff Bus Terminal 2-channel analog input KL3142
Beckhoff Bus Terminal 2-channel analog input KL3444
Beckhoff Bus Terminal 2-channel analog input KL3021
Beckhoff Bus Terminal 2-channel analog input KL3051