The EL2808 digital output terminal connects the binary 24 V DC control signals from the automation device on to the actuators at the process level with electrical isolation. The EtherCAT Terminal contains eight channels whose signal state is indicated by LEDs. The power contacts are connected through. In the EL2808 the outputs are supplied via the 24 V DC power contact.
Special features:
Connection of different load types possible (ohmic, inductive, lamp load)
Max. output current 0.5 A per channel
Overload and short-circuit proof outputs and reverse polarity protection
Tool-free connection by direct plug-in technology for solid wire conductors
Increased packing density with 16 connection points in the housing of a 12 mm terminal block
Connection technology:2-wire
Number of outputs:8
Nominal voltage:24 V DC (-15%/+20%)
Load type:ohmic, inductive, lamp load
Distributed clocks:–
Max. output current:0.5 A (short-circuit proof) per channel
Short-circuit current:typ. < 2 A
Reverse voltage protection:yes
Breaking energy:< 150 mJ/channel
Switching times:typ. TON: 60 μs, typ. TOFF: 300 μs
Current consumption E-bus:typ. 110 mA
Electrical isolation:500 V (E-bus/field potential)
Current consumption power contacts:typ. 15 mA + load
Bit width in the process image:8 outputs
Configuration:no address or configuration setting
Weight:approx. 65 g
Operating/storage temperature:-25…+60°C/-40…+85°C
Relative humidity:95%, no condensation
Vibration/shock resistance:conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission:conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.:IP20/variable
Approvals/markings:CE, UL, ATEX, IECEx
Housing data:EL-12-16pin
Design form:HD (High Density) housing with signal LEDs
Material:polycarbonate
Dimensions (W x H x D):12 mm x 100 mm x 68 mm
Installation:on 35 mm DIN rail, conforming to EN 60715 with lock
Side by side mounting by means of:double slot and key connection
Marking:labeling of the BZxxx series
Wiring:solid conductors (s): direct plug-in technique; fine-stranded conductors (st) and ferrule (f): spring actuation by screwdriver
EL2002 EtherCAT Terminal, 2-channel digital output, 24 V DC, 0.5 A
EL2004 EtherCAT Terminal, 4-channel digital output, 24 V DC, 0.5 A
EL2008 EtherCAT Terminal, 8-channel digital output, 24 V DC, 0.5 A
EL2014 EtherCAT Terminal, 4-channel digital output, 24 V DC, 0.5 A, with diagnostics
EL2809 EtherCAT Terminal, 16-channel digital output, 24 V DC, 0.5 A
EL2819 EtherCAT Terminal, 16-channel digital output, 24 V DC, 0.5 A, with diagnostics
EL1852 EtherCAT Terminal, 8-channel digital input + 8-channel digital output, 24 V DC, 3 ms, 0.5 A, flat-ribbon cable
EL1859 EtherCAT Terminal, 8-channel digital input + 8-channel digital output, 24 V DC, 3 ms, 0.5 A