Gastron GTD-5100F Explosion Proof Gas Detector
- It detects gases such as combustible / toxic / Freon / oxygen / VOC
- Self diagnosis function with built-in Microprocessor
- Easy replacement with a cartridge type sensor
- Digital flow sensor to maintain regular flow rate
- Fast response of gas leakage with a high efficient pump inside
- Stable quality and proved detection principle for service life
- Auto calibration and program setting with magnet bar on FND display board
- 4-Digit digital gas concentration display
- 4-20mA (Current source or Sink) output signal
- Easy configuration of monitoring by RS-485 Modbus communication
- 3-Wire Type | 2-stage alarm, 1-trouble display and relay contact output
- Calibration and maintenance by one-man
Measuring type
Accuracy
Parameter control
Operation mode display
Measuring value display
Alarm signal output
Output signal
Sampling method
Sampling line
Flow rate
Material
Conduit connection
Mounting type
Operating temperature
Operating humidity
Operating power
Auto sampling type
±3% / Full Scale
Non intrusive control with a Magnet bar (Calibration, Maintenance, Alarm setting)
GTD-5100F : Alarm / Trouble LED flow rate | LED indicator (Power, 2-Stage alarm, 1-Trouble)GTD-5100F LCD Version : 2.0" Color TFT LCD (Detector status, Gas info, Eror code etc) | LED indicator (Power, 2-stage alam, 1-Trouble)
GTD-5100F : FND display (4-Digit) | GTD-5100F LCD Version : 2.0" Color TFT LCD (Gas value, Flow rate etc.)
3.5A@30VDC,3.5A@125VAC(Resistive load)/3-SPST Relay contact (2-Stage alarm, 1-Trouble)
Analog 4-20mA, Relay,RS-485 Modbus (Option), PoE (Option)
Diaphragm pump
OD 1/4 "(Standard)
0~1000mL/min (Normal 500mL/min)
Steel
Standard : PF 3/4" | Option : NPT 3/4" M25 | PF 1/2" NPT 1/2" M20 (With Explosion proof reducer)
Wall mount
-10~60℃
5~99% RH (Non-condensing)
Dimensions200(W) x161(H)x139(D) mm
Weight 4kg
Standard type : 9.6W @24VDC (Max)
PoE type : 10.1W @48VDC (Max)